Technical Data |
Prestige 50 70 120 |
|
|
| |
|
Prestige 50 |
Prestige 75 |
Prestige 120 |
|
Input min/max |
kW |
15/49.9 |
18.3/72 |
35/118 |
|
Max output 60/80°C |
kW |
48.4 |
69.9 |
114.9 |
|
Min output 60/80°C |
kW |
14.7 |
17.9 |
34.3 |
|
Efficiency 30% load (EN887) |
% |
107.8 |
107.8 |
107.1 |
|
SAP seasonal efficiency |
% |
90.3 |
90.3 |
90.3 |
|
CO emissions min/max |
mg/kWh |
20/45 |
20/52 |
|
|
NOx emissions (EN483) |
mg/kWh |
66/30 |
62/38 |
|
|
NOx classification |
|
5 |
5 |
5 |
|
Flue gas temp 60/80°C |
°C |
82 |
82 |
|
|
Flue gas temp 30/50°C |
°C |
40 |
40 |
|
|
Primary capacity |
L |
20 |
17 |
|
|
Boiler connections (male BSP) |
Æ |
1 1/4 |
1 1/4 |
1 1/2 |
|
Gas connection (male BSP |
Æ |
3/4" |
3/4" |
1" |
|
Flue connection |
Æ mm |
100/150 |
100/150 |
Conventional/Parallel |
|
Max flue length |
m |
20 |
20 |
|
|
Weight empty |
kg |
54 |
58 |
83 |
|
Weight full |
kg |
74 |
78 |
113 |
|
Natural gas flow rate - 20mb |
m3/h |
5.28 |
7.6 |
12.7 |
|
Pressure drop |
mbar |
30 |
74 |
80 |