The HeatMaster 201 Condenser is delivered with the following.

• HeatMaster insulated body and control panel
• Complete casing
• Flue connection with horizontal exhaust and gasket
• Hydraulic kit, including 4-way valve, pipe work and hydraulic fittings and shunt pump
• Gas burner with insulation and gasket
 
Dimensions
Technical Data HM201 Booster
    HM 201 Booster
    Natural Gas/LPG
Input - heating kW 60 to 220
Input - hot water kW 60 to 240
Output - heating kW 58.7 to 210.1
Output - hot water kW 58.7 to 225
Primary capacity L 245
Total capacity L 645
Heating surface area m2 5.3
Primary circuit pressure drop mbar 240
DHW tank pressure drop mbar 190
DHW connection (male BSP) Æ 2"
Primary connection (female BSP) Æ 2"
Flue connection Æ mm 250
Weight empty kg 580
Weight full kg 1221
Gas flow rate m3/h 25.4/9.81
Minimum working gas pressure mbar 20/37
 
Performance Data    
     
Litres in first 10 minutes 40°C 1745
Litres in first 10 minutes  45°C 1489
Litres in first 10 minutes  60°C 971
Litres in first hour 40°C 7100
Litres in first hour 45°C 5667
Litres in first hour 60°C 3534
Continuous flow 40°C Ltrs/hr 6425
Continuous flow 45°C Ltrs/hr 5039
Continuous flow 60°C Ltrs/hr 2914
Reheat time to 60°C min 28
 

 

 