Technical Data |
HM60 |
|
|
| |
|
HM 60N |
HM 60N |
|
Fuel |
|
OIL |
NAT GAS / LPG |
|
Input |
kW |
69.9 |
69.9 |
|
Maximum output |
kW |
62.5 |
63 |
|
Primary capacity |
L |
82 |
82 |
|
Total capacity |
L |
162 |
162 |
|
Heating surface area |
m2 |
2.46 |
2.46 |
|
Primary circuit pressure drop |
mbar |
54 |
54 |
|
DHW tank pressure drop |
mbar |
45 |
45 |
|
Flue circuit pressure drop |
mbar |
0.6 |
0.6 |
|
DHW connection (male BSP) |
Æ |
3/4" |
3/4" |
|
Primary connection (female BSP) |
Æ |
1 1/2" |
1 1/2" |
|
Flue connection |
Æ mm |
150 |
150 |
|
Burner air intake connection |
Æ mm |
n/a |
80 (BG2000) |
|
Weight empty |
kg |
229 |
229 |
|
Weight full |
kg |
391 |
391 |
|
Minimum working gas pressure |
mbar |
|
20(Nat Gas)/37(LPG) |
|
Gas flow rate |
m3/h |
|
7.40(Nat Gas)/2.86(LPG) |
|
Performance Data |
|
|
|
| |
|
|
|
|
Litres in first 10 minutes |
40°C |
474 |
474 |
|
Litres in first 10 minutes |
45°C |
378 |
378 |
|
Litres in first 10 minutes |
60°C |
245 |
245 |
|
Litres in first hour |
40°C |
1942 |
1942 |
|
Litres in first hour |
45°C |
1656 |
1656 |
|
Litres in first hour |
60°C |
1106 |
1106 |
|
Continuous flow 40°C |
Ltrs/hr |
1835 |
1835 |
|
Continuous flow 45°C |
Ltrs/hr |
1573 |
1573 |
|
Continuous flow 60°C |
Ltrs/hr |
1101 |
1101 |
|
Reheat time to 60°C |
min |
9 |
9 |