ACV - excellence in hot water
Home
ACV technology
Products
About ACV
News
Documentation (PDF)
Contacts
Home  >  ACV Products
Back 

 HeatMaster® 70-100...

High Efficiency Range

High performance heating and hot
water generator. Can also be used as a
stand alone hot water generator
capable of operating at an elevated
temperature.
 
Simple, Well Proven Performance
At the heart of the HeatMaster is a stainless steel cylinder through which the flue tubes pass. This is surrounded by a mild steel shell containing the primary water.

The outer shell extends down to the combustion chamber and around the flue tubes. The heat transfer surface is therefore much greater than that of standard direct fired water heater. A circulating pump fitted to the primary circuit moves the water around the tank,
heating it faster and maintaining an even temperature across the primary jacket.

The burner fires into the combustion chamber which indirectly heats the stainless steel cylinder containing the DHW. As with all Tank-in-Tanks, this is corrugated over its full height and suspended in the HeatMaster by its hot and cold water connections.

Self-descaling
The tank has freedom of movement: its walls expand and contract with the changes in pressure thus preventing scale forming on the walls. Finally, the cold
water injected strikes against the bottom of the tank and carries all suspended particles into the system, helping to prevent deposits forming in the tank. This unique self-descaling feature ensures that the boiler always operates with maximum efficiency.
 
BG2000-S/70 and BG2000-S/100 Burner
ACV has developed these burners specially for the HeatMaster 70 and 100 models. Part of the BG 2000-S air/gas premix burner range, they have a metal fibre (NIT) flame tube and smooth and nearsilent ignition and operation. They are ideal for use in applications where burner noise must be kept to a minimum.
 
Benefits & Features
• High performance combined boiler and water heater
• Stainless steel Tank-in-Tank design
• Choice of burner:
- Low-NOx premix gas or LPG (BG2000-S),
- Pressure jet natural gas or LPG (Riello)
- Pressure jet 28 sec or 35 sec oil (Riello)
• Can also be used as a stand-alone water heater
• Anti-Legionellae: hot water stored at a consistently high temperature
• Built-in primary circuit shunt pump
• Fully insulated with rigid polyurethane foam
• Stove enamelled casing
• Control panel including thermostats, combined temperature and pressure gauge, indicators and on/off switch
• Vented or unvented use, with mains pressure SystemPaks available
 
Dimensions

 

 
HM70
 
Technical Data HM70  
    HM70  HM70
Fuel   OIL NAT GAS/LPG
Input kW 69.9 69.9
Maximum output kW 63 63
Primary capacity L 108 108
Total capacity L 236 239
Heating surface area m2 3.14 3.14
Primary circuit pressure drop mbar 46 46
DHW tank pressure drop mbar 45 45
Flue circuit pressure drop mbar 0.6 0.6
DHW connection (male BSP) Æ 1" 1"
Primary connection (female BSP) Æ 1 1/2 " 1 1/2 "
Flue connection Æ mm 150 150
Burner air intake connection Æ mm n/a 80 (BG2000)
Weight empty kg 279 279
Weight full kg 518 518
Minimum working gas pressure mbar n/a 20(Nat gas)/37(LPG)
Gas flow rate m3/h n/a 7.40(Nat gas)/2.86(LPG)
 
Performance Data      
       
Litres in first 10 minutes  40°C 646 646
Litres in first 10 minutes  45°C 543 543
Litres in first 10 minutes  60°C 346 346
Litres in first hour 40°C 2133 2133
Litres in first hour 45°C 1794 1794
Litres in first hour 60°C 1219 1219
Continuous flow 40°C Ltrs/hr 1835 1835
Continuous flow 45°C Ltrs/hr 1573 1573
Continuous flow 60°C Ltrs/hr 1067 1067
Reheat time to 60°C min 16 16
 
HM100
 
Technical Data HM100    
    HM100 HM100
Fuel   OIL NAT GAS/LPG
Input kW 107 107
Maximum output kW 96.3 96.3
Primary capacity L 130 130
Total capacity L 330 330
Heating surface area m2 3.95 3.95
Primary circuit pressure drop mbar 83 83
DHW tank pressure drop mbar 180 180
Flue circuit pressure drop mbar 1.4 1.4
DHW connection (male BSP) Æ 1" 1"
Primary connection (female BSP) Æ 1 1/2 " 1 1/2 "
Flue connection Æ mm 150 150
Burner air intake connection Æ mm   100 (BG2000)
Weight empty kg 333 333
Weight full kg 663 663
Minimum working gas pressure mbar n/a 20(Nat gas)/37(LPG)
Gas flow rate m3/h n/a 8.99(Nat gas)/3.47(LPG)
 
Performance Data      
       
Litres in first 10 minutes  40°C 905 905
Litres in first 10 minutes  45°C 777 777
Litres in first 10 minutes  60°C 514 514
Litres in first hour 40°C 3172 3172
Litres in first hour 45°C 2680 2680
Litres in first hour 60°C 1813 1813
Continuous flow 40°C Ltrs/hr 2776 2776
Continuous flow 45°C Ltrs/hr 2379 2379
Continuous flow 60°C Ltrs/hr 1665 1665
Reheat time to 60°C min 13 13

 

 

 

 