Technical Data |
|
|
|
| |
|
HM71 |
HM101 |
|
Fuel |
|
NAT GAS/LPG |
NAT GAS/ LPG |
|
Input |
kW |
20 to 69.9 |
25 to 107/ 22 to 110 |
|
Output |
kW |
18.4 to 63 |
23 to 96.8/ 20.2 to 99 |
|
Primary capacity |
L |
108 |
130 |
|
Total capacity |
L |
239 |
330 |
|
Heating surface area |
m2 |
3.14 |
3.95 |
|
Primary circuit pressure drop |
mbar |
46 |
83 |
|
DHW tank pressure drop |
mbar |
45 |
180 |
|
Flue circuit pressure drop |
mbar |
0.6 |
1.4 |
|
DHW connection (male BSP) |
Æ |
1" |
1" |
|
Primary Connection (female BSP) |
Æ |
1 1/2" |
1 1/2" |
|
Flue connection |
Æ mm |
150 |
150 |
|
Burner air intake connection |
Æ mm |
80 (BG2000-M) |
100 (BG2000-M) |
|
Weight empty |
kg |
282 |
335 |
|
Weight full |
kg |
521 |
665 |
|
Minimum working gas pressure |
mbar |
20(Nat gas)
37(LPG) |
20(Nat gas)
37(LPG) |
|
Gas flow rate |
m3/h |
2.12 to 7.4(Nat
gas) |
2.65 to 11.32(Nat
gas) |
| |
|
0.82 to 2.86(LPG) |
0.9 to 4.5(LPG) |
|
Performance Data |
|
|
|
| |
|
|
|
|
Litres in first 10 minutes |
40°C |
646 |
905 |
|
Litres in first 10 minutes |
45°C |
543 |
777 |
|
Litres in first 10 minutes |
60°C |
346 |
514 |
|
Litres in first hour |
40°C |
2133 |
3172 |
|
Litres in first hour |
45°C |
1794 |
2680 |
|
Litres in first hour |
60°C |
1219 |
1813 |
|
Continuous flow 40°C |
Ltrs/hr |
1835 |
2776 |
|
Continuous flow 45°C |
Ltrs/hr |
1573 |
2379 |
|
Continuous flow 60°C |
Ltrs/hr |
1067 |
1665 |
|
Reheat time to 60°C |
min |
16 |
13 |