ACV - excellence in hot water
Home
ACV technology
Products
About ACV
News
Documentation (PDF)
Contacts
Home  >  ACV Products
Back 

 SmartLine SLE Plus

FR Cylinder Range

Fast recovery Tank-in-Tank cylinder
– Built with heat pumps in mind…

Based on the proven Tank-in-Tank design, ACV have adapted the SLE cylinder to get the most out of any Heat Pump installation. By adding multiple connections you can now connect a Heat Pump directly into the primary tank allowing your Heat Pump to not only serve your heating system but also benefit your domestic hot water! A greater heat transfer surface means Tank-in-Tank units recover much faster than any other type of hot water storage cylinder – Keeping boiler cycling to a minimum, and ultimately giving improved fuel efficiency with outstanding hot water delivery.

High Outputs – Fast Recovery
At a time when consumers are demanding ever higher performance from their hot water installations, the traditional coil-based cylinder is often hard-pressed to keep up with demand. ACV Tank-in-Tank technology represents a significant advance in the science of hot water storage... so much so that, in virtually every situation encountered, the coil-based cylinder is completely out-classed.

Tank-In-Tank Technology
ACV’s advanced implementation of thermal storage technology is tried and tested and is remarkably simple, efficient and reliable. An inner stainless steel hot water cylinder is heated by primary water circulating through a surrounding outer tank connected to the boiler in the usual way. A much larger heat transfer surface means that Tank-in-Tank units recover much faster than any other kind of hot water storage device - and keeps boiler cycling to a minimum.

Resistance to Scaling
The special design of the inner cylinder not only helps ensure scale-free operation but also avoids the sediment problems that plague conventional cylinders.

Below is an example of the new SLE Plus connected to a Heat Pump system

Dimensions

SLE Plus 210/240/300 – 7 heating connections

SLE 130/160 – 2 heating connections

       

SLE PLUS

Technical Data

SLE

SLE 130

SLE 160

SLE 210

SLE 240

SLE 300

Total capacity

L

130

161

203

242

293

Primary capacity

L

55

62

77

78

93

Heating surface area

m2

1.03

1.26

1.54

1.94

2.29

Primary pressure drop

mbar

17

22

37

45

51

Primary flow rate

Ltrs/hr

2100

2600

3500

4200

5300

Maximum useable input

kW

23

31

39

53

66

Primary connections (F BSP)

Æ

1"

1"

1"

1"

1"

Hot water connections (M BSP)

Æ

3/4"

3/4"

3/4"

3/4"

3/4"

Immersion connection (F BSP)

Æ

1"1/2

1"1/2

1"1/2

1"1/2

1"1/2

Weight empty

kg

55

65

75

87

102

Weight full

kg

185

226

278

329

395

Maximum primary pressure

bar

3

3

3

3

3

Maximum hot water pressure

bar

10

10

10

10

10

Maximum operating temperature

°C

85

85

85

85

85

 
       

SLE PLUS

Performance Data

 

 SLE 130

SLE 160

210 SLE

240 SLE

300 SLE

Litres in first 10 minutes 

40°C

236

321

406

547

700

Litres in first 10 minutes 

45°C

202

275

348

469

600

Litres in first 10 minutes 

60°C

117

161

209

272

337

Litres in first hour

40°C

784

1063

1349

1820

2319

Litres in first hour

45°C

672

911

1156

1560

1988

Litres in first hour

60°C

384

549

689

913

1165

Continuous flow 40°C

Ltrs/hr

658

890

1132

1527

1943

Continuous flow 45°C

Ltrs/hr

564

763

970

1309

1665

Continuous flow 60°C

Ltrs/hr

320

465

576

769

994

Initial heat up time 10°C to 85°C

min

22

22

20

20

20

 

SLE Plus 210/240/300

SLE 130/160

Site map | Legal notice | Glossary | FAQ